Voltage Drop
Copper-run drop, remaining length and load, and a meter reading compared to the calculated drop.
Voltage drop calculator
Gauge, remaining length and load, and a meter reading compared to the calculated drop. Inputs stay in the URL.
Starting points
Inputs
Power Supply
Changing this resets the actual output reading to the nominal voltage.
What your meter reads at the power supply terminals.
The current rating printed on the supply.
Load
Current the device actually draws, not the supply rating.
Cable Run
One-way distance from the power supply to the device.
The AWG on the run, or the AWG under consideration.
Stranded class B is typical security and control cable.
Doubling the spare pair in 18/4 divides loop resistance by two.
Conditions
Default 68 °F / 20 °C. Switching units converts the value.
Reference temperatures
Acceptance
Window around the nominal rating, not a flat percent of drop.
Results
23.02 V at the device. Voltage at the device (23.02 V) is inside the 21.60–26.40 V window.
Voltage at the device
23.02V
Voltage at the device (23.02 V) is inside the 21.60–26.40 V window.
This run
Voltage drop
0.98V
Percent drop
4.07%
Target window
21.60–26.40V
Resistance (Ω/kft)
6.513 @ T20 °C 6.385
Smallest gauge that passes
21AWG
Room left
Max one-way length
368.5ft
Max device load
1.23A
Margin to lower limit
1.42V
Worked example
12 VDC, 1.5 A, and 180 ft of 18 AWG solid drops about 3.45 V and lands near 8.6 V at the device. That voltage is outside a ±10% window on 12 V (10.8–13.2 V). Combinations that land inside the window include a larger conductor, more conductors per leg, a higher supply voltage, a shorter run, or a local supply.
How to use
- Enter the supply rating and what it actually reads, the load, one-way length, conductor type, and temperature. When the run is outside the window, Options that pass at these conditions lists the combinations that land inside.
- After a gauge is selected, Room left shows the maximum one-way length and maximum load that still pass, plus the volt margin to the bottom of the window.
- A measured voltage at the device is compared to the expected voltage and implied loop resistance. Extra drop indicates something besides the copper that was entered.
Assumptions
- Solid annealed copper at 20 °C from the table in this app. Stranded class B multiplies resistance by 1.02. Fine-strand or tinned (1.08) is in the data table for review, not a third control. Temperature correction is then applied. These are not NEC 75 °C values.
- Paralleled conductors divide loop resistance by the number used per leg — the same move as doubling the spare pair in 18/4.
- AC circuits at these gauges and lengths are treated as purely resistive, so reactance is ignored.
- The round trip is two legs of the same gauge. Commonly stocked sizes in this trade are 22, 20, 18, 16, 14, and 12 AWG; every passing gauge is listed.
- The result is an estimate. Manufacturer data, the AHJ, and current applicable code govern material and whether a circuit is energized.
FAQ
- Why does a hot attic run fail when the same run passes in winter?
- Copper resistance rises with temperature. A 120 °F rooftop or attic run uses a higher R_T than the same length at 68 °F, so voltage at the device drops. A run that passes at 68 °F can fall outside the window at 120 °F.
- Why does the tolerance window matter more than a flat percent drop?
- The window is built from the nominal rating (for example 10.8–13.2 V on 12 VDC at ±10%), not a flat percent of whatever the supply happens to read. A supply sitting high can hide a long run; a supply sitting low can fail a short one.
- What accounts for measured drop above the calculated drop?
- Extra loop resistance is the first number to read. Conditions that produce it include a nicked or damaged conductor, a bad splice or termination, a partial short or ground, corroded connections, aluminum or copper-clad instead of solid copper, or a run longer than the value entered. The warning is a list of those conditions, not a diagnosis.
Disclaimer
Field estimate only. Manufacturer data, the authority having jurisdiction (AHJ), and current applicable code govern material and whether a circuit is energized. See the disclaimer.